Abacus Group Ltd. (201)
384-5552
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Location |
Panel |
Circuit/Fuse |
Temp. Increase |
Photo # |
Bldg. #7 |
KoHpump |
all |
0.0 |
1 |
Bldg. #7 |
CV1O6 Bot. Conv. |
all |
0.0 |
2 |
Bldg. #7 |
P207-HF Pump |
all |
0.0 |
3 |
Bldg. #7 |
PP3 |
#2 |
15.3 |
4 |
Bldg. #7 |
PP2 |
all |
0.0 |
n/a |
Bldg. #7 |
2OHP Scrubber fan wires |
9.3 |
5 | |
Bldg. #19A |
Boiler Room |
3 connectors |
22.3 |
6 |
The sets of thermograms depict thermal anomalies seen during the electrical survey. The information supplied on each page is as follows:
1. Building Section
2. Photo Set Number
3. Panel Designation
4. Circuit Number
5. Ambient Temperature
6. Anomaly Temperature
7. Temperature Increase from Ambient
8. Priority Scale
For Panel Designation, refer to the information listed on the Illustrations Page, the Infrared Analysis Summary (for location), and to the Visible Light Photograph (for exact panel designation).
Circuit Numbers and/or fuses listed in this section were confirmed with the infrared camera imagery and identified visually (as marked on the panel boxes).
Priority Scale can be interpreted as the following: All identified anomalies require attention in some form or another. The greater the temperature increase, the greater the importance of identifying the cause. Temperature increases seen at 10 degrees F. or less are not listed, as they can be assumed to be normal working temperatures. Increases that are seen as 10 degrees F. to 19 degrees F. are marked as Priority 3 on the thermogram pages. These circuits may or may not have a problem, as the temperature increases may be normal for those circuits. It is suggested, however to evaluate the circuits for potential problems as time and materials permit. Parts are usually repairable.
Temperature increases of 20 degrees to 49 degrees F. are marked as Priority 2, indicating a greater possibility of circuitry problems. Try to correct the problems soon. Parts are still usually repairable, but may become permanently damaged soon.
Circuits listed with temperature increases of 50 degrees F. and higher, are marked as Priority 1 and should take top priority in electrical service. Parts will often require replacement due to thermal stress. Attempts to simply tighten connections will probably not offer permanent repair.
|
|
|
Infrared Thermogram 1 |
Infrared Thermogram 6 |
|
|
|
|
Visible Light Photo 1 |
Visible Light Photo 6 |
|
| LOCATION | Bldg. #7 |
Bldg. #7 |
| PANEL | KOH Pump |
CV106 Bottle Convertor |
| CIRCUIT | all |
all |
| TEMP. INCREASE |
0 F |
0 F |
ELECTRICAL SURVEY RECOMMENDATIONS
At a minimum, a
preventative maintenance program should include the
following items:
1. Check and clean wiring connection points.
2. Take an amp reading at each identified circuit or
fuse.
Special attention should be made at anomalies with temperatures of 20 ° or more above ambient temperatures. Connections should be tightened and amp readings taken, to be sure the circuit is not overloaded. If an overload is determined, the usage of the circuit should be re-directed.
Thermal anomalies identified at wires may indicate that either the line is being overloaded or the wires are insufficient for the load being used. Check wires at identified anomalies to be sure they are the proper size.
Maintenance repair duties should be conducted by qualified electrical specialists, as working on indicated anomaly areas may be hazardous. For example, the affected circuit should be de-energized due to the high risk to personnel when tightening components in place on live apparatus. This is due to the possibility that insulating materials between conductors or ground have deteriorated or carbonized to a point where torque tightening pressure would cause final breakdown through that insulating medium. The maintenance mechanic would then be in direct contact with a bolted or ground fault condition. Also, connections of hardware or pole pieces may have annealed due to excessive heating causing reduced strength. Torquing pressure might then destroy the connection hardware, again subjecting the mechanic to fault condition hazards.
It should also be noted that burrs of foreign material may prevent the seating and surface conductivity of bolts and washers, etc. Torque tightening may then actually be ineffective although tightening is registered. In view of this possibility and in the interest of true cost effective power continuity, bus bar connections, or circuit breaker pole pieces should be disassembled, cleaned with slow residue solvent and re-silvered.
It is recommended that all deficiencies as described in this report, be addressed through proper maintenance and repair, and be re-scanned subsequent to their repair. This will insure proper corrective measures were taken.
To further explain the irregularities that are depicted in infrared inspections, we are providing further information on some of the most common problems.
1. ELEVATED FUSE BODY OR
BREAKER HOUSING TEMPERATURES
Fuse body/breaker housing temperatures may be elevated
for several different reasons.
The fuse/breaker may be overloaded (in excess of 80% of
its rated capacity) due to:
a) additional permanent and temporary loads being added
to the circuit,
b) the load may be straining or previously strained due
to mechanical reasons (i.e.,. dirt, improper lubrication,
modified tooling, previous motor seizure or failure,
etc),
c) voltage drops (primarily due to poor connections)
prior to or at the fuse.
Fuses/breakers very often display an elevated body temperature due to simple internal degradation. The internal connectors wear and become loose due to normal cycling of the unit. Also when temporary load strains weaken but do not completely fail the fusible link/thermal element, this will effectively lower the fuses/breakers ability to operate at its rated capacity.
All of these circumstances will cause your fusing to fail premature. In cases such as internal degradation and voltage drops it will cause failure without any apparent reason and often at the most inopportune times.
2. ELEVATED CONNECTOR TEMPERATURES
Although elevated connector temperatures are primarily due to loose connections, they may be due to a poor connection as well (i.e.,. conductor strands that are cut or bent away from the connector, dirt accumulations and conductor insulation inside the connection).
If a connector is just simply tightened, even at low temperature rises, dirt may be compressed in the connection creating tiny gaps in the connector that may lead to arcing and pitting. At high temperature rises, when arcing and pitting is present, if the connector is just imply tightened the pits and subsequent carbon accumulations will allow arcing and pitting to continue. This will usually provide only an improvement or temporary repair of the problem.
We recommend that the connection be removed, cleaned and inspected (both lug and conductor or spade) prior to tightening the connection. When a temperature rise above 50 degrees F is noted, ensure that arcing and pitting is not present, but if it is detected, it would be best to replace the affected connector parts.
3. ELEVATED CONDUCTOR TEMPERATURES
Elevated conductor temperatures may be caused by utilizing an undersized conductor or a properly sized conductor that has broken, cut or bent strands at both connections. These situations will cause the conductor to have a very constant elevated temperature over the entire length. Whereas if the conductor had broken or cut strands in the center of its length it would cause the temperature to elevate in that area.
Conductor may also have elevated temperatures when they are over-crowded in conduit or cable trays and also in situations when simply too many are tied together.
4. ELEVATED SPRING CLIP CONNECTOR TEMPERATURE
Spring clip failure is commonly caused by improper removal and installation of the fuse (i.e.,. using screwdrivers, etc.) causing the spring clip to become bent or deformed and not allowing a proper connection to the fuse. These are very difficult to simply bend or tighten due to the tendency for it to deform at a different area when attempting to repair the original problem.
We recommend that the spring clip be replaced and inspect the fuse head for arcing and pitting and replace it as necessary, especially since the fuse is often degraded due to conductive heat or subsequent voltage drops created by the defective spring clip.
5. ELEVATED BEARING HOUSING TEMPERATURES
Bearing failures are
commonly caused by overlubrication/overpressurization.
The most common cause of overlubrication is the lack of
an adequate program and tracking system. If over or under
lubrication is indicated and you are uncertain of the
lubrication frequency and volume, it would be difficult
to determine how to best correct the situation. We have
found it to be extremely beneficial to either utilize a
form of log or bearing tag to document your program. The
critical information to be recorded is:
a) Bearing Identification
b) Standard Lubricant
c) Standard Lubrication Frequency
d) Standard Lubrication Volume
e) Date of Lubrication
f) Amount of Lubricant Added
g) Name of Lubricator
This information will not only allow you and your staff to make adjustments due to missed lubrication frequencies and lack of communication between lubricators, it will allow you to make simple adjustments when either under or over lubrication is determined.
For more information on all of the above Corrective Actions, please contact Abacus Group Ltd.